High performance variable torque drive for Fan & Pump
(V/F mode / Sensorless Vector mode / V/F + PG mode / Vector + PG mode)
230V, 3-Phase : 0.75 ~ 90kW (1 ~ 120Hp)
460V, 3-Phase : 1.5 ~ 400kW (2 ~ 535Hp)
575V, 3-Phase : 0.75 ~ 630kW (2 ~ 850Hp)
Features
16 Bit Microprocessor Sensor less vector control
V/F mode & Sensor less Vector mode-------open loop control
V/F + PG mode & Vector + PG mode---------close loop control
Auto tuning
Over load capability 125%, 1 minute
Automatic torque boost & slip compensation
Output frequency 0.1~600Hz, Programmable
16-step PLC run & 16 step preset speed
PID feedback control & PG feedback control
2 accel./decel time selection (0.01~60000 sec)
Pump control and automatic energy -saving.
Process follower - 10~10VDC, 0~10VDC, 4~20mA
MODBUS communication RS-485 (Baud rate 125000 bps)
Coast or ramp to stop
Random V/F curve & Automatic voltage regulation (AVR)
Auto-optimum accel./decel. time & S-curves
Sleep/Wakeup function & Auto Restart after fault
Mechanical braking release control function
Auto Restart after fault & Fault history up to 16 records
Module/ Heatsink temperature display & Pre-warning
Low noise-- Carrier frequency up to 18 kHz
Bi-Directional Speed search (Reentry to spinning load)
Password protection & User define Multi-function display
DC bus capacitor life time monitoring & Auto carrier frequency adjust
Over-current/Over-voltage stall prevention & Over torque detection
Full protection (LV,OV,OC,SC,OH,OL…etc.)
Programmable Multi-Function input terminals
Programmable Multi-Function output terminals
Programmable Analog output voltage & current signals
Programmable Digital pulse output
Encorder style knob with 0.01Hz resolution
Removable Keypad operator up to 150 meters.
Sink/Source (NPN/PNP) mode selectable by user
DC injection brake & Dynamic brake
Electronic Thermal Relay & External Counter built-in
Fan & Pump process control (Time/Fix amount circulation control)
Model Names
Topvert P1 Series: 3-Phase, 200-240VAC, 50/60 Hz (Tolerance Range: 180-264V, 47-63Hz) |
Model |
Motor
(230V, 4 Pole) |
Rated Output |
Power Source |
Enclosure Construction |
P1-xxxxx |
Power
(kW) |
Horse Power (Hp) |
Capacity
(kVA) |
Current
(A) |
Voltage
(V) |
Frequency
(Hz) |
Current
(A) |
Cooling Methods |
Protection |
Weight Net/Gross
(kg) |
Cubic
(CBM) |
Frame Code |
230P7 |
0.75 |
1 |
1.4 |
3.6 |
3-Phase
0-240 (Max.) |
0.1~600 |
4 |
Fan-cooled
|
IP 20
|
2.6/3.0 |
0.0178 |
P1-A
|
231P5 |
1.5 |
2 |
2.3 |
6 |
6.6 |
2.8/3.2 |
232P2 |
2.2 |
3 |
3.4 |
9 |
9.9 |
2.8/3.3 |
233P7 |
3.7 |
5 |
5 |
13 |
14.5 |
2.8/3.2 |
235P5 |
5.5 |
7.5 |
7.8 |
20 |
22.4 |
3.0/3.4 |
237P5 |
7.5 |
10 |
11.4 |
30 |
33 |
3.2/3.7 |
23011 |
11 |
15 |
15.1 |
40 |
43.6 |
4.0/4.6 |
0.0211 |
P1-B
|
23015 |
15 |
20 |
22.4 |
59 |
65 |
11.9/13.0 |
0.0515 |
P1-C
|
23018 |
18.5 |
25 |
29.7 |
78 |
86 |
12.3/13.5 |
23022 |
22 |
30 |
34.3 |
90 |
99 |
13.0/14.2 |
23030 |
30 |
40 |
41.2 |
108 |
119 |
13.5/14.7 |
23037 |
37 |
50 |
54.9 |
144 |
158 |
IP 00
|
32.7/36.5 |
0.1802 |
P1-D
|
23045 |
45 |
60 |
66.8 |
175 |
193 |
37.5/41.2 |
0.2082 |
P1-E
|
23055 |
55 |
75 |
83.2 |
218 |
240 |
38.3/42.1 |
23075 |
75 |
100 |
101 |
264 |
290 |
58.0/63.9 |
0.3357 |
P1-F
|
23090 |
90 |
120 |
137 |
360 |
396 |
59.4/65.4 |
Topvert P1 Series: 3-Phase, 380-480VAC, 50/60 Hz (Tolerance Range: 342-528V, 47-63Hz) |
Model |
Motor
(460V, 4 Pole) |
Rated Output |
Power Source |
Enclosure Construction |
P1-xxxxx |
Power
(kW) |
Horse Power (Hp) |
Capacity
(kVA) |
Current
(A) |
Voltage
(V) |
Frequency
(Hz) |
Current
(A) |
Cooling Methods |
Protection |
Weight Net/Gross
(kg) |
Cubic
(CBM) |
Frame Code |
431P5 |
1.5 |
2 |
2.7 |
3.6 |
3-Phase
0-460 (Max.) |
0.1~600 |
4 |
Fan-cooled |
IP 20
|
2.8/3.2 |
0.0178 |
P1-A |
432P2 |
2.2 |
3 |
3.8 |
5.0 |
6 |
2.9/3.3 |
433P7 |
3.7 |
5 |
5.5 |
7.2 |
8 |
2.9/3.3 |
435P5 |
5.5 |
7.5 |
7.8 |
10 |
11 |
2.9/3.3 |
437P5 |
7.5 |
10 |
11.9 |
16 |
17 |
3.0/3.5 |
43011 |
11 |
15 |
16.5 |
22 |
24 |
3.3/3.8 |
43015 |
15 |
20 |
21.9 |
29 |
32 |
4.3/4.9 |
0.0211 |
P1-B |
43018 |
18.5 |
25 |
29.3 |
38 |
42 |
5.0/5.6 |
43022 |
22 |
30 |
34.8 |
48 |
50 |
13.0/14.1 |
0.0515 |
P1-C |
43030 |
30 |
40 |
41.2 |
58 |
59 |
13.0/14.1 |
43037 |
37 |
50 |
55 |
72 |
79 |
13.9/15.1 |
43045 |
45 |
60 |
67 |
96 |
96 |
IP 00
|
33.5/37.3 |
0.1802 |
P1-D |
43055 |
55 |
75 |
83 |
116 |
120 |
33.5/37.3 |
43075 |
75 |
100 |
101 |
142 |
145 |
33.5/37.3 |
43090 |
90 |
120 |
137 |
182 |
198 |
37.1/41.0 |
43110 |
110 |
150 |
165 |
216 |
238 |
42.4/46.1 |
0.2082 |
P1-E |
43132 |
132 |
175 |
201 |
288 |
290 |
63.0/68.9 |
0.3357 |
P1-F |
43160 |
160 |
215 |
238 |
324 |
343 |
64.5/70.4 |
43185 |
185 |
250 |
283 |
365 |
409 |
64.5/70.4 |
43220 |
220 |
300 |
337 |
444 |
486 |
|
|
P1-G |
43280 |
280 |
375 |
366 |
540 |
528 |
|
43315 |
315 |
420 |
444 |
624 |
642 |
|
43400 |
400 |
535 |
540 |
732 |
779 |
|
Topvert P1 Series: 3-Phase, 575-600VAC, 50/60 Hz (Tolerance Range: 342-528V, 47-63Hz) |
Model |
Motor
(575V, 4 Pole) |
Rated Output |
Power Source |
Enclosure Construction |
P1-xxxxx |
Power
(kW) |
Horse Power (Hp) |
Capacity
(kVA) |
Current
(A) |
Voltage
(V) |
Frequency
(Hz) |
Current
(A) |
Cooling Methods |
Protection |
Weight Net/Gross
(kg) |
Cubic
(CBM) |
Frame Code |
630P7 |
0.75 |
1 |
1.5 |
1.4 |
3-Phase
0-460 (Max.) |
0.1~600 |
|
Fan-cooled |
IP 20
|
|
|
P1-A |
631P5 |
1.5 |
2 |
2.8 |
2.7 |
|
|
|
632P2 |
2.2 |
3 |
4.1 |
3.9 |
|
|
|
633P7 |
3.7 |
5 |
6.3 |
6.1 |
|
|
|
635P5 |
5.5 |
7.5 |
9.4 |
9 |
|
|
|
637P5 |
7.5 |
10 |
11.4 |
11 |
|
|
|
63011 |
11 |
15 |
17.7 |
17 |
|
|
|
P1-B |
63015 |
15 |
20 |
22.9 |
22 |
|
|
|
63018 |
18.5 |
25 |
28.1 |
27 |
|
|
|
P1-C |
63022 |
22 |
30 |
33.3 |
32 |
|
|
|
63030 |
30 |
40 |
42.6 |
41 |
|
|
|
63037 |
37 |
50 |
54 |
52 |
|
IP 00
|
|
|
P1-D |
63045 |
45 |
60 |
64.4 |
62 |
|
|
|
63055 |
55 |
75 |
80 |
77 |
|
|
|
63075 |
75 |
100 |
102.9 |
99 |
|
|
|
63090 |
90 |
120 |
129.9 |
125 |
|
|
|
P1-E |
63110 |
110 |
150 |
145.5 |
140 |
|
|
|
63132 |
132 |
175 |
181.9 |
175 |
|
|
|
P1-F |
63160 |
160 |
215 |
223.4 |
215 |
|
|
|
63180 |
180 |
250 |
259.8 |
250 |
|
|
|
63220 |
220 |
300 |
311 |
300 |
|
|
|
63280 |
280 |
375 |
389 |
375 |
|
|
|
P1-G |
63315 |
315 |
420 |
436.5 |
420 |
|
|
|
63400 |
400 |
535 |
55.6 |
535 |
|
|
|
63450 |
450 |
600 |
627.7 |
604 |
|
|
|
63500 |
500 |
670 |
717 |
690 |
|
|
|
63560 |
560 |
750 |
810.6 |
780 |
|
|
|
Specifications
Max. Applicable Motor
Output Range (kW/Hp) |
3-phase, 200 ~ 230VAC, 50/60Hz: 0.75 ~ 90kW (1 ~ 120Hp) |
3-phase, 380 ~ 460VAC, 50/60Hz: 1.5 ~ 400kW (2~ 535Hp) |
3-phase, 575 ~ 600VAC, 50/60Hz: 1.5 ~ 630kW (2~ 850Hp) |
Output |
Output Frequency |
0.1 ~ 600Hz |
Overload Endurance |
150% of rated current for 1 minute/10minute, Ta <=40 ; 200% of rated current for 2 seconds |
Maximum Output Voltage |
Proportional to Input Voltage, 3-Phase |
Power factor / Efficiency |
Power factor no lower than 0.95. Efficiency no lower than 95% at full load (97% for >22kW models). |
Control Characteristics |
Control System |
SPWM (Sinusoidal Pulse Width Modulation), V/F control and Sensorless Vector Control selectable |
|
|
Speed Control |
V/F Control 1:20; Sensorless Control 1:50; V/F + PG Close-Circuit 1:100; Sensorless + PG Close-Circuit 1:100 |
Frequency Setting Range |
0 .10 - 600Hz, programmable |
Frequency Setting Resolution |
0.01Hz/step |
PWM Carrier Frequency |
1kHz - 18kHz Adjustable (Restrictions on some models) |
Torque Characteristics |
Including the auto-torque, auto-slip compensation; starting torque can be 150% at 1.0Hz |
Skip Frequency |
3 points |
Accel/Decel Time |
0.1-6000 seconds (2 Independent settings for Accel/Decel Time) |
Stall Prevention Level |
10 to 250%, Setting of Rated Current. Setting range 0.1-600Hz while stop. |
DC Braking |
DC Braking Current Level: 0 to 125% of rated output current. DC Braking time: 0 to 60 seconds. Start-Point for DC Braking: 0.1-600Hz both when start up and stop. |
Dynamic Braking Torque |
Approx. 20%, Dynamic Brake chopper built-in in Frame code: P1-A and P1-B. Others can be built-in as an option. All models can connect to external Dynamic Brake unit module (DBU) |
V/F Pattern |
Adjustable V/F curve using 4 independent points. |
Operating Characteristics |
Frequency Setting |
Keypad |
By a rotary encoder (setting resolution 0.01Hz/step) |
External Signal |
~ +10VDC (Input impedance 20k Ω ), -10 ~ +10VDC (Input impedance 10k Ω ), 4 ~20mA DC ( Input impedance 250 Ω ), Multi-Function Inputs 1 ~ 6 (15 Steps Jog, up/down ), PLC run , RS-485 serial interface MODBUS protocol |
Operation Setting |
|
Set by RUN, STOP and JOG key |
External Signal |
FWD, REV, MI1 to MI6 can be combined to offer various modes of operation, RS-485 serial interface MODBUS protocol |
Multi-Function Input Signal
(6 signals) |
Multi-step selection 0 to 15, first to second accel/decel switches, accel/decel inhibit, EF Input, Emergency Stop, auxiliary motor control is invalid, ACI/AVI/AUI speed command selection, Reset, PLC Run , Jog, Up/Down command, Sink/Source selection
|
Multi-Function Output Indication (5 indications) |
Drive Operating, Frequency Attained, Non-zero, Base Block, Fault Indication, Local/Remote indication, PLC Operation indication, and Auxiliary Motor Output |
Analog Output Signal |
Analog signal output proportional to output frequency, output current, voltage, frequency command or motor's speed |
Fault Indication |
The output will be activated when faults occur (1 Relay contact point RA, RB, RC. or 2 Open-collector output) |
Communication |
RS-485 serial interface MODBUS protocol |
|
PID feedback control, automatic voltage regulation, Momentary Power Loss restart, S-Curve, External Fault, Fault Reset, Auto Restart, Fault Records, Frequency Limits, Fan & Pump Control, Parameter Lock/Reset, Auto Tuning, Reverse Inhibition, Over-Voltage/ Over-Current Stall Prevention, automatic energy-saving, DC Braking, Speed Search during Start-up, PLC, MODBUS Communication |
|
Self-testing, AC source Over Voltage, Over Voltage, Over Current, Under Voltage, Over Load, Overheating, External Fault, Electronic thermal, Ground Fault, Stall Prevention, Output short circuit , IGBT short circuit |
Digital Keypad
(Option) PU-02 with Copy Function
(Option) PU-03 with LCD Display and Operation
|
8 Function keys |
Access Run, Stop, Reset/ Digit Shift, Forward/ Reverse run, Display mode, Keypad Enable, Programming data and Jog operation. |
360 degree Rotary Encoder |
Sets the parameter number and changes the numerical data |
6 digits 7 segment display |
Display the Setting frequency/actual operation frequency, Output current/Voltage, User defined unit, |
Six LED Display for status indication |
Display the AC drive's run/stop status, forward/Reverse run status, Keypad enable, and Frequency command source. |
Removable Keypad |
Remote control distance up to 150 meters. |
|
CE Safety |
Meet LVD: EN50178 standards; When combining with Toptek's filter, meet EMC: EN61800-3 standards
|
UL Safety |
Meet UL508C standards |
Temperature |
Ambient: -10°C ~ +40 °C ( Non-Condensing and not frozen ). Storage: -20°C ~ +60°C |
Humidity |
Below 98% R. H. (Non-Condensing) |
Vibration |
Below 20Hz: 1G, above 20Hz: 0.6G |
Installation Location |
Altitude 1,000 m or lower, keep away from corrosive gasses, liquid and dust |
|