High performance general purpose compact drive
(V/F mode / Sensorless Vector mode)
110V, 1-Phase : 0.2-1.5kW (0.25-2Hp)
230V, 1-Phase : 0.2-2.2kW (0.25-3Hp)
230V, 3-Phase : 0.4-7.5kW (0.5-10Hp)
460V, 3-Phase : 0.4-7.5kW (0.5-10Hp)
Features
16 Bit Microprocessor Sensor less vector control
V/F mode & Sensor less Vector mode
Auto tuning
Over load capability 150%, 1 minute
Automatic torque boost & slip compensation
Output frequency 0.1~600Hz, Programmable
16-step PLC run & 16 step preset speed
PID feedback control & PG feedback control
2 accel./decel time selection (0.01~60000 sec)
Pump control and automatic energy -saving.
Process follower - 10~10VDC, 0~10VDC, 4~20mA
MODBUS communication RS-485 (Baud rate 125000 bps) (optional)
Coast or ramp to stop
Random V/F curve & Automatic voltage regulation (AVR)
Auto-optimum accel./decel. time & S-curves
Sleep/Wakeup function & Auto Restart after fault
Mechanical braking release control function
Auto Restart after fault & Fault history up to 16 records
Module/ Heatsink temperature display & Pre-warning
Low noise-- Carrier frequency up to 18 kHz
Bi-Directional Speed search (Reentry to spinning load)
Password protection & User define Multi-function display
DC bus capacitor life time monitoring & Auto carrier frequency adjust
Over-current/Over-voltage stall prevention & Over torque detection
Full protection (LV,OV,OC,SC,OH,OL...etc.)
Programmable Multi-Function input terminals
Programmable Multi-Function output terminals
Programmable Analog output voltage & current signals (optional)
Programmable Digital pulse output (optional)
Encorder style knob with 0.01Hz resolution
Removable Keypad operator up to 150 meters.
Sink/Source (NPN/PNP) mode selectable by user
DC injection brake & Dynamic brake
Electronic Thermal Relay & External Counter built-in
Easy DIN rail mounting
Model Names
Topvert E1 Series: 1-Phase, 100-120VAC, 50/60 Hz (Tolerance Range: 90-132V, 47-63Hz)
Output: 200-240VAC |
Model |
Motor
(230V, 4 Pole) |
Rated Output |
Power Source |
Enclosure Construction |
E1-xxxxx |
Power
(kW) |
Horse Power (Hp) |
Capacity
(kVA) |
Current
(A) |
Voltage
(V) |
Frequency
(Hz) |
Current
(A) |
Cooling Methods |
Protection |
Weight Net/Gross
(kg) |
Cubic
(CBM) |
Frame Code |
110P2 |
0.2 |
0.25 |
0.6 |
1.6 |
3-Phase
0-240 (Max.) |
0.1~600 |
6.1 |
Fan-cooled |
IP 20
|
|
0.0084 |
E1-A
|
110P4 |
0.4 |
0.5 |
1.2 |
3 |
11.4 |
|
110P7 |
0.75 |
1 |
2 |
5 |
19.1 |
|
111P5 |
1.5 |
2 |
3 |
7.5 |
28.6 |
|
Topvert E1 Series: 1-Phase, 200-240VAC, 50/60 Hz (Tolerance Range: 180-264V, 47-63Hz) |
Model |
Motor
(230V, 4 Pole) |
Rated Output |
Power Source |
Enclosure Construction |
E1-xxxxx |
Power
(kW) |
Horse Power (Hp) |
Capacity
(kVA) |
Current
(A) |
Voltage
(V) |
Frequency
(Hz) |
Current
(A) |
Cooling Methods |
Protection |
Weight Net/Gross
(kg) |
Cubic
(CBM) |
Frame Code |
210P2 |
0.2 |
0.25 |
0.6 |
1.6 |
3-Phase
0-240 (Max.) |
0.1~600 |
3 |
Fan-cooled |
IP 20
|
1.5/1.8 |
0.0084 |
E1-A
|
210P2A |
|
0.0066 |
E1-S |
210P4 |
0.4 |
0.5 |
1.2 |
3 |
5.7 |
1.5/1.9 |
0.0084 |
E1-A
|
210P4A |
|
0.0066 |
E1-S |
210P7 |
0.75 |
1 |
2 |
5 |
9.5 |
1.6/1.9 |
0.0084 |
E1-A
|
210P7A |
|
0.0066 |
E1-S |
211P5 |
1.5 |
2 |
3 |
7.5 |
14.3 |
1.6/2.0 |
0.0084 |
E1-A
|
211P5A |
|
0.0066 |
E1-S |
212P2 |
2.2 |
3 |
4.4 |
11 |
|
1.7/2.0 |
0.0084 |
E1-A
|
Topvert E1 Series: 3-Phase, 200-240VAC, 50/60 Hz (Tolerance Range: 180-264V, 47-63Hz) |
Model |
Motor
(230V, 4 Pole) |
Rated Output |
Power Source |
Enclosure Construction |
E1-xxxxx |
Power
(kW) |
Horse Power (Hp) |
Capacity
(kVA) |
Current
(A) |
Voltage
(V) |
Frequency
(Hz) |
Current
(A) |
Cooling Methods |
Protection |
Weight Net/Gross
(kg) |
Cubic
(CBM) |
Frame Code |
230P4 |
0.4 |
0.5 |
1.2 |
3 |
3-Phase
0-240 (Max.)
|
0.1~600 |
3.3 |
Fan-cooled |
IP 20
NEMA 1 |
1.5/1.9 |
0.0084 |
|
230P4A |
|
0.0066 |
E1-S |
230P7 |
0.75 |
1 |
2 |
5 |
5.5 |
1.6/1.9 |
0.0084 |
|
230P7A |
|
0.0066 |
E1-S |
231P5 |
1.5 |
2 |
3 |
7.5 |
8.3 |
1.6/1.9 |
0.0084 |
|
231P5A |
|
0.0066 |
E1-S |
232P2 |
2.2 |
3 |
4.4 |
11 |
12.1 |
1.6/2.0 |
0.0084 |
|
233P7 |
3.7 |
5 |
6.8 |
17 |
|
|
(235P5) |
5.5 |
7.5 |
10 |
25 |
27.5 |
|
|
(E1-B) |
(237P5) |
7.5 |
10 |
13 |
33 |
|
|
Topvert E1 Series: 3-Phase, 380-460VAC, 50/60 Hz (Tolerance Range: 342-528V, 47-63Hz) |
Model |
Motor
(460V, 4 Pole) |
Rated Output |
Power Source |
Enclosure Construction |
E1-xxxxx |
Power
(kW) |
Horse Power (Hp) |
Capacity
(kVA) |
Current
(A) |
Voltage
(V) |
Frequency
(Hz) |
Current
(A) |
Cooling Methods |
Protection |
Weight Net/Gross
(kg) |
Cubic
(CBM) |
Frame Code |
430P4 |
0.4 |
0.5 |
1.3 |
1.6 |
3-Phase
0-460 (Max.) |
0.1~600 |
1.8 |
Fan-cooled |
IP 20
|
1.6/1.9 |
0.0084 |
E1-A
|
430P7 |
0.75 |
1 |
2.4 |
3 |
3.3 |
1.6/1.9 |
431P5 |
1.5 |
2 |
3.3 |
4.2 |
4.6 |
1.6/2.0 |
432P2 |
2.2 |
3 |
4.8 |
6 |
6.6 |
1.6/2.0 |
0.0084 |
E1-A
|
433P7 |
3.7 |
5 |
6.8 |
8.5 |
|
|
(435P5) |
5.5 |
7.5 |
10 |
13 |
14.3 |
|
|
(E1-B) |
(437P5) |
7.5 |
10 |
14 |
18 |
|
|
Remark:
1.Frame code E1-S is compact size of E1-A
2.( )means not available.
Specifications
Max. Applicable Motor
Output Range (kW/Hp) |
1- phase, 100 ~ 120VAC, 50/60Hz:0.2 ~ 1.5kW (0.25 ~ 2Hp) |
1- phase, 200 ~ 240VAC, 50/60Hz:0.2 ~ 2.2kW (0.25 ~ 3Hp) |
3-phase, 200 ~ 230VAC, 50/60Hz:0.4 ~ 7.5kW (0.5 ~ 10Hp) |
3-phase,380 ~ 460VAC, 50/60Hz:0.4 ~ 7.5kW (0.5~ 10Hp) |
Output |
|
0.1 ~ 600Hz |
|
150% of rated current for 1 minute/10minute, Ta <=40 ;200% of rated current for 2 seconds |
|
Proportional to Input Voltage, 3-Phase (For 100V class, output voltage is twice of the input voltage) |
Power factor / Efficiency
|
Power factor no lower than 0.95. Efficiency no lower than 95% at full load |
Control Characteristics |
|
SPWM (Sinusoidal Pulse Width Modulation), V/F control and Sensorless Vector Control selectable |
|
V/F Control 1:20; Sensorless Control 1:50 |
Frequency Setting Range |
0.10 - 600Hz,programmable |
Frequency Setting Resolution |
0.01Hz/step |
PWM Carrier Frequency |
1kHz - 18kHz Adjustable (Restrictions on some models) |
Torque Characteristics |
Including the auto-torque, auto-slip compensation; starting torque can be 150% at 1.0Hz |
Skip Frequency |
3 points |
Accel/Decel Time |
0.1-6000 seconds (2 Independent settings for Accel/Decel Time |
Stall Prevention Level |
10 to 250%, Setting of Rated Current. Setting range 0.1-600Hz while stop |
DC Braking |
DC Braking Current Level: 0 to 125% of rated output current. DC Braking time: 0 to 60 seconds. Start-Point for DC Braking: 0.1-600Hz both when start up and stop. |
Dynamic Braking Torque |
Approx. 20%,Dynamic Brake chopper built-in. |
V/F Pattern |
Adjustable V/F curve using 4 independent points. |
Operating Characteristics |
Frequency Setting |
Keypad |
By a rotary encoder (setting resolution 0.01Hz/step) |
External Signal |
0 ~ +10VDC (Input impedance 20k Ω ), 4 ~20mA DC ( Input impedance 250 Ω ), Multi-Function Inputs 1 ~ 6 (15 Steps Jog, up/down ), PLC run , (Option) RS-485 serial interface MODBUS protocol |
Operation Setting |
|
Set by RUN, STOP and JOG key |
External Signal |
FWD, REV, MI1 to MI6 can be combined to offer various modes of operation, (Option) RS-485 serial interface MODBUS protocol |
Multi-Function Input Signal (6 signals) |
Multi-step selection 0 to 15, first to second accel/decel switches, accel/decel inhibit, EF Input, Emergency Stop, auxiliary motor control is invalid, ACI/AVI/AUI speed command selection, Reset, PLC Run , Jog, Up/Down command, Sink/Source selection |
Multi-Function Output Indication( 2 signals, extra 3 signals as option) |
Drive Operating, Frequency Attained, Non-zero, Base Block, Fault Indication, Local/Remote indication, PLC Operation indication, and Auxiliary Motor Output |
Analog Output Signal (option) |
Analog signal output proportional to output frequency, output current, voltage, frequency command or motor's speed. |
Fault Indication |
The output will be activated when faults occur (1 Relay contact point RA, RB, RC. or 2 Open-collector output) |
Communication |
(Option) RS-485 serial interface MODBUS protocol |
|
PID feedback control, automatic voltage regulation, Momentary Power Loss restart, S-Curve, External Fault, Fault Reset, Auto Restart, Fault Records, Frequency Limits, Fan & Pump Control, Parameter Lock/Reset, Auto Tuning, Reverse Inhibition, Over-Voltage/ Over-Current Stall Prevention, automatic energy-saving, DC Braking, Speed Search during Start-up, PLC, MODBUS Communication |
|
Self-testing, AC source Over Voltage, Over Voltage, Over Current, Under Voltage, Over Load, Overheating, External Fault, Electronic thermal, Ground Fault, Stall Prevention, Output short circuit , IGBT short circuit |
Digital Keypad
(Option) PU-02 with Copy Function
(Option) PU-03 with LCD Display and Operation
|
8 Function keys |
Access Run, Stop, Reset/ Digit Shift, Forward/ Reverse run, Display mode, Keypad Enable, Programming data and Jog operation. |
360 degree Rotary Encoder |
Sets the parameter number and changes the numerical data |
6 digits 7 segment display |
Display the Setting frequency/actual operation frequency, Output current/Voltage, User defined unit. |
Six LED Display for status indication |
Display the AC drive's run/stop status, forward/Reverse run status, Keypad enable, and Frequency command source |
Removable Keypad |
Remote control distance up to 150 meters. |
|
CE Safety |
Meet LVD: EN50178 standards; When combining with Toptek's filter, meet EMC: EN61800-3 standards |
UL Safety |
Meet UL508C standards |
Temperature |
Ambient: -10°C ~ +40 °C ( Non-Condensing and not frozen ). Storage: -20°C ~ +60°C |
Humidity |
Below 98% R. H. (Non-Condensing) |
Vibration |
Below 20Hz: 1G, above 20Hz: 0.6G |
Installation Location |
Altitude 1,000 m or lower, keep away from corrosive gasses, liquid and dust |
|