Model (TDBU-xxxx) |
2015 |
2022 |
4030 |
4045 |
4132 |
6055 |
Maximum Motor Capacity (kW) |
15 |
22 |
30 |
45 |
132 |
55 |
Suitable for Drive source (ACV) |
200 to 240 |
380 to 480 |
575 to 600 |
Power Input Rating (DCV) |
200 to 400 |
400 to 800 |
607 to 1000 |
Output Rating |
Max. Discharge Current (Amp. peak) 10% ED |
40 |
60 |
40 |
60 |
240 |
60 |
Continuous Discharge Current (Amp.) |
15 |
20 |
15 |
18 |
75 |
20 |
Minimum equivalent resistor for each Braking Unit |
10Ω |
6.8Ω |
20Ω |
13.6Ω |
3.4Ω |
15.8Ω |
Braking Start-up Voltage (DCV) |
330/345/360/380/
400/415
±3V, Selectable |
620/660/690/720/
760/800/830
±6V, Selectable |
950 ±8V |
Protection |
Heat Sink Overheat |
Temperature over +95°C (203°F) |
Alarm Output |
Relay contact, 5A120VAC/28VDC (RA, RB, RC) |
Power Charge Display |
Lit on when DC bus voltage is above 50VDC |
Environment |
Installation Location |
Indoor (no corrosive gases, metallic dust) |
Operating Temperature |
-10°C ~+50°C (14°F to 122°F) |
Storage Temperature |
-20°C~+60°C (-4°F to 140°F) |
Humidity |
90% Non-condensing |
Vibration |
9.8m/s2 (1G) under 20Hz, 2m/s2 (0.2G) at 20~50Hz |
Mechanical Configuration |
Wall-mounted enclosed type IP20 (NEMA 1) |
Enclosure |
Frame code |
TDBU-A |
TDBU-B |
TDBU-A |